The GZDW Battery Charge Cabinet is a DC power conversion and battery charging system designed for installations that require a dedicated DC supply for protection, control, switching and other critical electrical loads.
Technical Specifications
|
Parameter |
Specification |
|
Product Series |
GZDW DC Power Supply System |
|
DC System Voltage |
110V / 220V |
|
Rated DC Current |
6–400A |
|
Battery Capacity |
10–3000Ah |
|
AC Input |
Two independent three-phase, four-wire AC supplies |
|
Rated AC Input |
380V ±10%, 50Hz ±5% |
|
Charging Technology |
High-frequency switching rectifier modules |
|
Rectifier Configuration |
Parallel modular operation, N+1 redundancy |
|
Battery Types |
Vented lead-acid, VRLA, Ni-Cd |
|
Control |
PLC or SCM |
|
Operating Mode |
Continuous operation |
|
Ambient Temperature |
-10°C to +45°C |
|
Maximum Altitude |
≤2400m |
|
Relative Humidity |
Daily average ≤95%; monthly average ≤90% |
|
Seismic Requirement |
Earthquake magnitude ≤8 |
|
Equipment Noise |
<55 dB(A), measured under the specified test condition |
Charger Selection Note
Charger capacity is selected from the continuous DC load, required battery charging current and specified reserve capacity. Battery Ah rating alone is not sufficient for charger selection.
Continuous DC Load + Battery Charging Requirement + Reserve Capacity → Charger Capacity
Battery Charging

Float Charging
Maintains the battery at its specified standby charging condition during normal operation.
Equalizing Charging
Provides the higher charging condition required by the selected battery and operating procedure.
Automatic Current Limitation
Restricts charging current within the configured operating range.
Charging voltage and current are configured according to the selected battery manufacturer's technical data.
Protection & System Monitoring
The charging system incorporates protection functions for defined abnormal electrical conditions, including:
- Input overvoltage protection
- Output overvoltage protection
- Overcurrent protection
- Short-circuit protection
- Automatic current limitation
Monitoring
The monitoring points are defined according to the selected system configuration and can cover:
- AC input status
- DC output status
- Charging status
- Protection status
- Fault status
- Alarm status
Remote signals and communication interfaces are configured according to the plant or substation control requirements.
DC Loads and Applications
The DC distribution section supplies circuits defined by the project load schedule.
Typical DC loads include:
Circuit breaker trip circuits
Circuit breaker closing circuits
Relay protection circuits
Control circuits
Signaling circuits
Other specified DC auxiliary circuits
Typical applications include:
Substations
Protection, breaker operation, control and signaling systems requiring a stationary DC supply.
Power Plants
DC systems serving designated electrical protection, switching and control circuits.
Industrial Electrical Systems
Dedicated DC supplies for industrial protection and control applications.
Measured Rectifier Module Performance
The 240D05A rectifier module has been tested for voltage regulation, current regulation, dynamic response, efficiency, ripple, dielectric strength and parallel current sharing.
|
Test Item |
Representative Result |
Test Condition |
|
Voltage Regulation Accuracy |
0.01% |
20–100% load, 300–456VAC input |
|
Current Regulation Accuracy |
0.08% |
20–100% load, 300–456VAC input |
|
Dynamic Response |
50μs |
20–75% load step |
|
Efficiency |
90% |
300V DC, 5A output |
|
Ripple Factor |
0.01–0.1% |
0–20MHz |
|
Dielectric Strength |
1500VAC |
50Hz, 1 minute |
|
Parallel Current Imbalance |
±0.5% |
Rated input and output |
FAQ
Q: What is the typical lead time for a DC battery charger cabinet?
A: The standard lead time is 7–15 days after order confirmation and receipt of the 30% advance payment, subject to the final order quantity and agreed configuration.
Q: What are your payment terms? Is a deposit required?
A: The payment terms are 30% advance payment and 70% balance before shipment.
Q: Can customers specify preferred component brands?
A: Yes. Customer-specified component brands can be considered and included in the agreed bill of materials when they meet the required technical specifications and interfaces.
Q: Can you provide OEM or private-label service?
A: OEM service can be arranged for qualified orders, including agreed product labeling, nameplates and related documentation.
Q: Can you provide a quotation based on a customer's bill of materials?
A: Yes. A customer-provided bill of materials can be reviewed and reflected in the quotation and agreed supply scope.
Q: What is included in the quotation?
A: The quotation can specify the equipment scope, agreed configuration, documentation, packing, delivery terms, payment terms and quotation validity.
Q: Can the equipment be inspected before shipment?
A: Yes. Pre-shipment inspection can be arranged according to the agreed inspection requirements, including customer or third-party inspection where specified in the purchase agreement.
Q: Can export packaging be provided for international shipment?
A: Yes. Export packaging can be arranged according to the cabinet dimensions, shipment method and destination requirements to protect the equipment during transportation.
Q: Can spare parts be supplied with the equipment?
A: Spare parts can be quoted according to the selected equipment configuration and the buyer's maintenance requirements.
Q: Can technical documents be provided in English?
A: Yes. The required technical documentation can be prepared in English according to the agreed project and document submission requirements.
Q: How can I request a quotation?
A: Send your available technical specification, project requirements, drawings or existing equipment information together with your commercial requirements. Our sales and engineering teams can then review the information and prepare a quotation based on the confirmed scope.