LV and MV Panels are electrical assemblies for low- and medium-voltage power distribution, switching and protection. LV panels serve downstream distribution and motor circuits, while MV panels handle incoming supply, feeders and transformer connections.

Technical Specifications
The following electrical ratings refer to the documented KYN28-12 MV configuration.
|
Parameter |
Specification |
|
Product Range |
LV and MV Panels |
|
MV Configuration |
KYN28-12 |
|
Rated Voltage |
3 / 6 / 10 kV |
|
Rated Frequency |
50 Hz |
|
Rated Current |
630 / 1000 / 1250 / 1600 / 2000 / 2500 / 3150 A |
|
Rated Short-Time Withstand Current |
20 / 25 / 31.5 / 40 kA |
|
Rated Peak Withstand Current |
50 / 63 / 80 / 100 kA |
|
Rated Short-Circuit Duration |
4 s |
|
Power-Frequency Withstand Voltage |
42 kV / 1 min |
|
Withstand Voltage Across Isolating Distance |
48 kV / 1 min |
|
Lightning Impulse Withstand Voltage |
75 kV |
|
Lightning Impulse Withstand Voltage Across Isolating Distance |
85 kV |
|
Enclosure Protection |
IP4X |
|
Internal Compartment Protection |
IP2X |
|
MV Circuit Breaker |
VS1 / VD4 Vacuum Circuit Breaker |
|
Installation |
Indoor |
Panel Construction
LV Panel Construction
Main Distribution Section
The incoming section accommodates the main switching device and connects to the LV busbar system. The arrangement is defined by the incoming circuit rating and required distribution topology.
Feeder and Motor Sections
Outgoing circuits are arranged according to the connected loads, with ACB, MCCB or other specified switching devices mounted according to the circuit configuration.
Busbar and Cable Arrangement
Main and distribution busbars are positioned according to the current rating and internal layout. Cable entry and termination areas are coordinated with feeder quantity, cable size and routing direction.
Enclosure and Access
Mounting plates, doors, cable spaces and operating access are arranged around the selected equipment and required service access.
MV Panel Construction
Circuit Breaker Section
The vacuum circuit breaker is installed in the designated switching area, with the mechanical arrangement coordinated with the panel operating and connection requirements.
Busbar Section
The main busbar system provides the electrical connection between incoming and outgoing circuits. Busbar clearances and connection interfaces follow the specified electrical configuration.
Cable Section
The lower cable area accommodates incoming or outgoing cable connections and associated components required by the circuit arrangement.
Control and Auxiliary Section
The control and auxiliary compartment provides the mounting and wiring space required for secondary circuits and associated operating components.
Protection, Control and Metering
Protection: Protection relays and associated measurement components are selected according to the specified protection scheme.
Control: Control and auxiliary circuits are arranged for the required switching and operating functions.
Metering: Measurement and indication functions are configured according to the required electrical data.

Panel Configuration Scope
Panel configuration is defined from the project electrical schedule, physical constraints and required equipment rather than from a standard panel layout.
The project configuration may define:
Circuit Schedule: Incoming, outgoing and coupling circuit quantities.
Equipment Schedule: Required breakers, switches, protection and measurement devices.
Site Constraints: Panel dimensions, lineup sequence, cable entry and access direction.
Project Documentation: Approved drawings, equipment schedules and required technical records.
Factory Verification
Each completed LV or MV panel is checked against the approved drawings, component list and electrical configuration before shipment. Verification is performed on the assembled panel before final release.
Mechanical Verification
Fabrication and Assembly: Enclosure dimensions, formed sections, mounting interfaces and component fit are checked against the approved layout.
Operating Mechanisms: Switching mechanisms, doors, locks and specified mechanical functions are operated to confirm correct movement.
Interlocking: Specified mechanical interlocks are operated to verify the defined switching sequence.
Connections and Access: Cable connection areas, terminals and access points are checked against the approved arrangement.
Electrical Verification
Wiring: Main, auxiliary and control wiring is checked against the approved electrical schematic.
Continuity and Insulation: Circuit continuity and insulation performance are verified before shipment.
Dielectric Testing: Dielectric tests are performed where required by the applicable specification.
Functional Checks: Control, indication, switching and specified protection functions are checked against the approved configuration.
Final Inspection
Factory test records are completed and retained against the corresponding panel before shipment. Final inspection verifies the assembled panel against the approved configuration and required project documentation.
FAQ
Q: What is the minimum order quantity for LV and MV panels?
A: The minimum order quantity is normally 1 panel or 1 complete panel lineup. Multi-panel projects are quoted according to the required quantity and configuration.
Q: What payment terms are available for LV and MV panel orders?
A: Common payment terms include T/T and L/C. The final payment structure is confirmed in the quotation and sales contract according to the order and project requirements.
Q: What is the typical lead time for LV and MV panels?
A: Production typically takes 15–30 working days after technical confirmation and receipt of the agreed advance payment. Larger lineups, special components or additional testing requirements may require a longer production schedule.
Q: How are LV and MV panels packaged for international shipment?
A: Panels are protected with export-grade packaging. Plywood cases or equivalent protection are selected according to panel dimensions, weight and transport conditions.
Q: Which Incoterms are available for LV and MV panel orders?
A: FOB, CIF, CFR and EXW can be used for international orders. The applicable Incoterm, destination port and freight arrangement are confirmed in the commercial quotation.
Q: What information is needed to receive a quotation for LV and MV panels?
A: Provide the required quantity, destination country or port, electrical ratings, preferred commercial terms and available tender or purchasing documents. For project orders, a single-line diagram, electrical specification or equipment schedule can be provided to define the quotation scope.