Medium Voltage Panels

Medium Voltage Panels

The KYN61-40.5 Medium Voltage Panel is an indoor metal-clad withdrawable switchgear assembly for receiving and distributing three-phase AC power, with circuit switching, protection, control and measurement functions.
Send Inquiry
Description
Technical Parameters

The KYN61-40.5 Medium Voltage Panel is an indoor metal-clad withdrawable switchgear assembly for receiving and distributing three-phase AC power, with circuit switching, protection, control and measurement functions.

 

product-307-296

 

Technical Specifications

 

Parameter

Specification

Product Series

KYN61-40.5

Product Type

Indoor metal-clad withdrawable medium voltage switchgear

Rated Voltage

40.5 kV

Rated Frequency

50 Hz

Rated Current

1250 / 1600 / 2000 / 2500 A

Rated Short-Circuit Breaking Current

20 / 25 / 31.5 kA

Rated Short-Time Withstand Current

20 / 25 / 31.5 kA, 4 s

Rated Peak Withstand Current

50 / 63 / 80 kA

Rated Short-Circuit Making Current

50 / 63 / 80 kA

Power-Frequency Withstand Voltage, 1 min

95 kV

Lightning Impulse Withstand Voltage

185 kV

Auxiliary and Control Circuit Power-Frequency Withstand Voltage

2 kV / 1 min

Control Circuit Rated Voltage

DC 110/220 V; AC 110/220 V

Enclosure Protection

IP4X

Protection with Compartment Door Open

IP2X

Installation

Indoor

 

Panel Construction


Busbar Compartment
Houses the main busbar and associated insulating components.
Busbar bushings provide insulated interfaces between the busbar section and associated primary circuits.


Handcart Compartment
Houses the withdrawable circuit breaker assembly.
The circuit breaker is mounted on a movable handcart for movement within the cabinet.


Cable Compartment
Provides the connection area for incoming or outgoing power cables and associated primary equipment.


Instrument Compartment
Accommodates secondary control, measurement and protection equipment.
The secondary equipment is separated from the main high-voltage sections within the cabinet.


Pressure Release Device
Provides a defined pressure-discharge path from the relevant compartment when abnormal internal conditions cause pressure to build up.
This pressure-release provision does not by itself establish an internal-arc classification for the switchgear.

 

Switching & Safety


The KYN61-40.5 combines a withdrawable circuit breaker, mechanical interlocking, position indication and an earthing switch to control switching operations and restrict defined incorrect operating sequences.


Switching
The circuit breaker is mounted on a withdrawable handcart, allowing the switching assembly to be moved within the cabinet and providing circuit interruption within its specified capability.


Interlocking & Position Indication
Mechanical interlocking restricts defined incorrect operating sequences between the circuit breaker handcart and operating mechanism. Position indication provides an operating reference for the state of the withdrawable assembly.


Earthing
The earthing switch is operated as part of the applicable switching and interlocking sequence for the relevant primary circuit.

 

Primary Circuit Components


The primary circuit connects the feeder cable, circuit breaker and main busbar, with current transformers and an earthing switch integrated into the feeder circuit.


Primary Power Path
The cable connection provides the feeder interface, while the withdrawable circuit breaker controls switching between the feeder circuit and main busbar. The primary contact interface connects the withdrawable breaker with the fixed primary circuit.


Current Transformer
Current transformers provide secondary current signals for applicable protection and measurement circuits.


Earthing Switch
The earthing switch provides the designated earth connection for the relevant primary circuit during the applicable earthing procedure.


Secondary Plug
The secondary plug provides the control and signal interface between the withdrawable assembly and associated secondary equipment.

 

Quality Control


The KYN61-40.5 panel is controlled against the confirmed technical specification and project requirements from production review through pre-shipment inspection.


Technical Verification
Before production, the ordered electrical ratings, circuit arrangement, primary components, control requirements and project specifications are reviewed against the approved technical information.


Configuration Control
The approved technical configuration is used as the production reference. Changes affecting the ordered equipment are subject to technical review and updated in the applicable project documentation.


Pre-Shipment Inspection
The inspection scope and acceptance criteria are confirmed against the ordered equipment and project requirements. Inspection results are recorded in the equipment quality documentation.


Quality Documentation
Applicable drawings, technical documents and inspection records can be provided according to the agreed order and project requirements.

 

Engineering & RFQ


The KYN61-40.5 configuration is evaluated from the project electrical scheme, feeder arrangement and protection requirements rather than from the product model alone.

 

RFQ Information

Typical Requirements

Electrical System

Rated voltage, frequency, current and short-circuit level

System Diagram

Single-line diagram and feeder arrangement

Feeder Requirements

Incoming, outgoing and transformer feeders

Bus Arrangement

Bus-coupler or bus-section requirements, where applicable

Protection & Measurement

CT, voltage measurement, protection and metering requirements

Control

Control functions and control circuit voltage

Cable Connection

Incoming or outgoing cable connection requirements

Quantity & Arrangement

Panel quantity and equipment arrangement

Project Documents

Technical specifications, drawings and equipment schedules

Acceptance Requirements

Project-specific inspection or acceptance requirements


The single-line diagram, electrical ratings and project requirements provide the engineering basis for evaluating the switchgear configuration and preparing the quotation.

 

FAQ

 

Q: What is the MOQ for KYN61-40.5 medium voltage panels?

A: The MOQ can start from 1 panel for project evaluation or small orders. Larger switchgear lineups are quoted according to the required number of panels, feeder arrangement and project configuration.

Q: What is the typical lead time for KYN61-40.5 panels?

A: The typical lead time is approximately 30–45 days for a standard project, depending on panel quantity, circuit configuration, component selection and drawing approval. The final delivery schedule is confirmed with the quotation and order.

Q: What payment terms are available for KYN61-40.5 panels?

A: T/T is available for KYN61-40.5 panel orders, with the payment schedule confirmed according to the order and project conditions. L/C and other payment arrangements can be discussed for applicable project orders.

Q: What technical documents are provided with the switchgear?

A: The documentation package can include approved technical drawings, wiring or secondary-circuit documents, product documentation, inspection records and other project-required files. The document list is confirmed during technical clarification and included in the order documentation.

Q: Can KYN61-40.5 panels be configured for different feeder arrangements?

A: A: Yes. The KYN61-40.5 can be configured for project-specific feeder and bus arrangements. The final configuration is confirmed from the approved single-line diagram and technical specification.

Q: Can customers specify component brands or approved vendors?

A: Yes. Customer-specified brands and approved vendor lists can be incorporated into the technical review. The selected components are confirmed before production to ensure compatibility with the required electrical ratings and switchgear configuration.

Q: Can customer or third-party inspection be arranged before shipment?

A: Yes. Customer or third-party inspection can be arranged before shipment when required by the project. The inspection scope, witness points, acceptance criteria and required inspection records are agreed before the inspection takes place.

Q: Can spare parts and replacement components be supplied?

A: Yes. Spare parts can be supplied with the switchgear or ordered separately for later maintenance. Recommended spare parts can be identified from the circuit breaker, operating mechanism, control circuit and other installed components, with the final list confirmed against the ordered configuration.

Q: How are KYN61-40.5 panels packed and prepared for shipment?

A: KYN61-40.5 panels can be prepared in export-grade wooden cases or other agreed protective packaging for overseas shipment. The packing method is determined according to the panel dimensions, equipment configuration, transportation method and destination, with packing lists and applicable shipping documents prepared for delivery.

Hot Tags: medium voltage panels, China medium voltage panels manufacturers, suppliers, factory, Electrical Ring Main Unit, Lv and Hv Switchgear, Medium Voltage Cabinet, Medium Voltage Panels, Metal Clad Medium Voltage Switchgear, Mvsg Electrical