Metal Clad Medium Voltage Switchgear

Metal Clad Medium Voltage Switchgear

KYN28-12 Metal Clad Medium Voltage Switchgear is an indoor metal-clad, withdrawable medium voltage switchgear assembly for three-phase AC power distribution at 50 Hz. The lineup is designed for medium-voltage power receiving, distribution, switching, protection, control and measurement in substations, power plants and industrial electrical systems.
Send Inquiry
Description
Technical Parameters

KYN28-12 Metal Clad Medium Voltage Switchgear is an indoor metal-clad, withdrawable medium voltage switchgear assembly for three-phase AC power distribution at 50 Hz. The lineup is designed for medium-voltage power receiving, distribution, switching, protection, control and measurement in substations, power plants and industrial electrical systems.

 

Electrical Ratings

 

Parameter

Specification

Model

KYN28-12

Product Type

Indoor metal-clad withdrawable medium voltage switchgear

Rated Voltage

3 kV, 6 kV, 10 kV

Voltage Class

12 kV

Rated Frequency

50 Hz

Rated Current

630 A to 3150 A

Rated Short-Time Withstand Current

20 kA, 25 kA, 31.5 kA, 40 kA

Rated Peak Withstand Current

50 kA, 63 kA, 80 kA, 100 kA

Rated Short-Circuit Duration

4 s

Rated Power Frequency Withstand Voltage

42 kV phase-to-phase / phase-to-ground; 48 kV across isolating distance

Rated Lightning Impulse Withstand Voltage

75 kV phase-to-phase / phase-to-ground; 85 kV across isolating distance

Enclosure Protection

IP4X

Internal Protection

IP2X

Installation

Indoor

Circuit Breaker

Withdrawable vacuum circuit breaker

Busbar System

Single busbar or single busbar sectionalized configuration

 

Metal-Clad Construction


Metal Enclosure: Aluminum-zinc coated steel panels are used for the cabinet enclosure and internal barriers.


Compartment Separation: Metal partitions separate the busbar, circuit breaker, cable and low-voltage sections according to the switchgear configuration.


Primary Circuit Separation: The primary circuit sections are physically separated from the low-voltage control equipment by dedicated barriers.

 

Internal Compartment Layout


Busbar Compartment: Contains the main and branch busbars, insulation components and primary connections between functional panels.


Circuit Breaker Compartment: Houses the withdrawable vacuum circuit breaker and fixed primary contact assembly used for the operating position.


Cable Compartment: Provides the termination space for incoming or outgoing cables, with room for CTs, grounding equipment and other cable-side components defined by the feeder arrangement.


Low-Voltage Control Compartment: Houses protection relays, metering devices, secondary terminals and breaker control circuits.

 

Withdrawable Vacuum Circuit Breaker


The KYN28-12 is equipped with a withdrawable vacuum circuit breaker. The breaker specification is matched to the feeder load, fault level and control scheme defined for each panel.


Breaker Rating: Rated current follows the feeder load, while the breaker short-circuit breaking capability is matched to the calculated fault level at the installation point.


Control Voltage: Closing and tripping circuits are connected to the specified auxiliary power supply.


Auxiliary Contacts: Auxiliary contacts provide the signals required for protection, control, indication and interlocking circuits.


Operating Mechanism: The operating mechanism provides the required closing and tripping sequence and interfaces with the switchgear interlocking system.


Protection Coordination: Breaker interrupting capability is checked against the feeder fault duty and protection scheme.

 

Protection, Metering & Secondary Control


The low-voltage section contains the protection, measurement and control devices associated with each feeder.


Protection: Protection relays receive current signals from CTs and provide the protection functions assigned to the feeder.


Voltage Measurement: VTs provide voltage signals for protection, metering and control where voltage measurement is required.


Metering & Control: Metering devices, breaker control circuits, status indication and external terminals are integrated into the low-voltage section.


Technical Configuration: The secondary design covers relay functions, CT/PT ratios, accuracy class, auxiliary supply and external control interfaces.

 

IMG2159
IMG2161

 

Typical Panel Functions


Incoming Feeder Panel
Receives the medium-voltage supply and incorporates the switching and protection equipment assigned to the incoming circuit.


Outgoing Feeder Panel
Feeds downstream circuits through the specified breaker, protection and measurement arrangement.


Transformer Feeder Panel
Connects the medium-voltage side of a transformer and accommodates the switching, protection and measurement equipment assigned to the transformer circuit.


Bus Section Panel
Provides the switching connection between designated busbar sections.


PT Panel
Provides voltage measurement signals for the protection, metering and control system.


Metering Panel
Integrates the specified electrical measurement equipment for feeder or system monitoring.

 

Quality Control


Cabinet Inspection
Panel dimensions, door alignment and compartment construction are checked during final assembly against the released general arrangement drawing.


Primary Circuit Inspection
Circuit breaker, CT/PT, grounding components and primary connections are verified against the equipment schedule and primary circuit configuration.


Busbar Inspection
Busbar dimensions, connection points, phase identification and insulation arrangement are inspected before the enclosure is closed.


Secondary Wiring Inspection
Wire identification, terminal connections and control circuits are checked against the released electrical schematic.


Mechanical Inspection
The breaker is operated through its specified positions to verify insertion, withdrawal and mechanical interlocking.


Electrical Testing
Routine electrical tests required by the applicable standard and approved project specification are completed before release.


Final Configuration Check
The finished panel is compared with the released drawings, component list and equipment schedule before shipment.


Inspection Records
Inspection and test results are recorded as part of the project quality documentation.

 

product-1170-891

 

FAQ

 

Q: What information is required to configure a KYN28-12 lineup?

A: The single-line diagram, system voltage, rated current, short-circuit level, feeder quantity, transformer data, cable termination requirements, protection scheme, metering requirements and auxiliary supply should be confirmed before configuration.

Q: How is the required short-circuit rating determined?

A: The required rating should be checked against the calculated fault level at the switchgear installation point and the specified short-time withstand current, peak withstand current and circuit breaker capability.

Q: What affects the final dimensions of a KYN28-12 lineup?

A: Panel functions, rated current, circuit breaker configuration, cable termination arrangement, CT/PT configuration, secondary equipment and panel quantity affect the final general arrangement.

Q: What documents are required before manufacturing starts?

A: The technical specification, single-line diagram, general arrangement drawing, electrical schematic, equipment schedule and project-specific protection and control requirements normally form the manufacturing release package.

Q: Can KYN28-12 be configured for an existing switchgear lineup?

A: Existing busbar arrangements, cable interfaces, protection requirements, panel dimensions and electrical ratings should be reviewed before confirming compatibility with an existing installation.

Q: What should be checked when selecting CTs and PTs for the switchgear?

A: CT/PT ratio, accuracy class, protection or metering function, burden requirements, insulation level and connection arrangement should be checked against the project protection and metering scheme.

Q: What should be confirmed before releasing a KYN28-12 order for production?

A: The purchaser should confirm that the approved drawings, technical specification, equipment schedule and protection and control requirements are consistent, and that all agreed deviations, component substitutions and project-specific requirements have been incorporated before production release.

Hot Tags: metal clad medium voltage switchgear, China metal clad medium voltage switchgear manufacturers, suppliers, factory, 35kV High Voltage Switchgear, Electrical Ring Main Unit, Low Medium Voltage Switchgear, Lv and Hv Switchgear, Medium Voltage Metal Enclosed Switchgear, medium voltage switchgear