Medium Voltage Switchgear Manufacturers is an indoor metal-clad withdrawable medium voltage switchgear assembly for AC power distribution, switching, protection and control.

Technical Specifications
|
Parameter |
Specification |
|
Product Type |
Indoor metal-clad withdrawable medium voltage switchgear |
|
Rated Voltage |
3.6~12 kV |
|
Rated Frequency |
50 Hz |
|
Rated Current |
630–3150 A |
|
Short-Circuit Breaking Current |
16–40 kA |
|
Short-Time Withstand Current |
16–40 kA, 4s |
|
Peak Withstand Current |
40–100 kA |
|
Power-Frequency Withstand Voltage |
24 / 32 / 42 kV, 1 min |
|
Lightning Impulse Withstand Voltage |
40 / 60 / 75 kV |
|
Circuit Breaker |
Withdrawable vacuum circuit breaker |
|
Enclosure Protection |
IP4X |
|
Cabinet Structure |
Four-compartment metal-clad construction |
|
Installation |
Indoor |
|
Cabinet Dimensions |
Approx. 2300 H × 800/1000 W × 1500–1660 D mm |
|
Referenced Standards |
GB 3906; GB/T 11022; DL/T 404; IEC 60298 (historical designation) |
Technical Note: Final electrical ratings, insulation levels, component selection and cabinet configuration are confirmed against the approved project specification and applicable technical documentation.
Construction & Main Components
Busbar Compartment
The main busbars and their insulation components are installed in the busbar compartment, forming the primary electrical connection between adjacent switchgear panels.
Circuit Breaker Compartment
Accommodates the withdrawable vacuum circuit breaker and operating mechanism. The withdrawable assembly provides defined service, test and disconnected positions.
Cable Compartment
Provides connection space for incoming or outgoing medium voltage cable terminations and associated primary connections.
Low-Voltage / Control Compartment
Contains protection relays, meters, control switches, terminal blocks and secondary wiring.
Main Components
- Withdrawable vacuum circuit breaker for switching and fault interruption
- Main busbar system for power distribution between panels
- Current transformers for protection and measurement
- Voltage transformers for voltage measurement and protection functions
- Earthing switch for grounding the relevant circuit under defined operating conditions
- Surge arresters where required by the electrical scheme
- Protection relays and metering equipment according to the panel function
Component selection follows the approved electrical ratings, panel function and project drawings.

Panel Functions
KYN28-12 can be arranged as different functional panels within a medium voltage switchgear lineup.
Incoming Panel: Connects the incoming power source to the main busbar through the specified switching, protection and measurement equipment.
Outgoing Feeder Panel: Transfers power from the main busbar to downstream distribution circuits, transformers or motors.
Bus Coupler Panel: Connects or separates two busbar sections according to the operating arrangement of the medium voltage distribution system.
Metering / PT Panel: Provides the voltage and current measurement arrangement required for metering, protection or control.
Transformer Feeder Panel: Connects the medium voltage busbar to a power transformer through the specified switching and protection equipment.
Panel functions and the final primary and secondary configuration are established from the approved single-line diagram and project technical requirements.
Safety & Protection
Interlocking: Mechanical and electrical interlocking coordinates the operating sequence of the circuit breaker, withdrawable mechanism, earthing switch and associated cabinet access points.
Earthing & Position Indication: The earthing arrangement provides grounding for the relevant circuit under the defined operating condition. Position indication identifies the breaker and withdrawable mechanism status during operation and maintenance.
Fault Protection: Protection relays provide the specified overcurrent and other feeder protection functions according to the configured protection scheme.
Pressure Relief:Pressure-relief paths are incorporated according to the cabinet construction to provide a defined route for internal fault pressure.



Typical Applications
Medium Voltage Substations
Incoming, outgoing and bus-section circuits within indoor medium voltage substations.
Industrial Power Distribution
Medium voltage distribution to transformers, motors and downstream electrical loads in industrial facilities.
Transformer Feeders
Dedicated medium voltage circuits connecting distribution switchgear to power transformers with specified switching and protection functions.
Medium Voltage Motor Feeders
Medium voltage motor circuits requiring switching, measurement and electrical protection.
Factory Inspection & Testing
Each KYN28-12 panel is assembled and inspected against the approved drawings, component list and technical configuration before shipment. Mechanical and control functions are verified before final inspection.
Assembly Inspection
- Cabinet dimensions and assembly
- Busbar installation and clearances
- Primary component installation
- Secondary wiring and terminal connections
- Mechanical assemblies
- Component identification
The completed assembly is checked against the approved drawings and component list.
Mechanical & Electrical Verification
- Circuit breaker operating mechanism
- Withdrawable mechanism operation
- Control circuit continuity
- Interlocking functions
- Secondary circuit connections
The verification sequence follows the approved electrical and mechanical drawings.
Final Inspection
- Nameplate data
- Wiring and terminal identification
- Component and accessory completeness
- Documentation
- Cabinet condition
- Export packing
The final inspection confirms that the supplied panel corresponds to the approved project configuration.
FAQ
Q: What information is required for KYN28-12 configuration and quotation?
A: Key information includes system voltage, rated current, short-circuit level, panel quantity, panel functions, cable arrangement, protection and metering requirements, control voltage and the project single-line diagram. The technical specification should also be provided where available.
Q: Can you supply a complete KYN28-12 switchgear lineup?
A: Yes. Complete switchgear lineups can be supplied with the required incoming, feeder, bus coupler, metering or transformer feeder panels based on the approved project configuration.
Q: Can replacement circuit breakers be supplied for an existing KYN28-12 lineup?
A: Replacement breakers must match the existing cabinet interface, electrical rating, truck mechanism and control circuit. Existing switchgear information should be reviewed before compatibility is confirmed.
Q: What is the MOQ for KYN28-12 switchgear?
A: MOQ depends on the required panel quantity and project scope. Individual panels and complete switchgear lineups can be reviewed based on project requirements.
Q: What is the typical lead time for KYN28-12 switchgear?
A: Lead time depends on panel quantity, component selection, engineering approval and production scheduling. The delivery schedule is confirmed after the technical configuration and order details are finalized.
Q: What manufacturing capability supports KYN28-12 production?
A: Worldwide Electric operates a 200,000+ m² manufacturing base with 120+ production and testing equipment and a reported annual capacity of 10,000+ sets of high- and low-voltage switchgear and related electrical equipment.
Q: How is KYN28-12 packaged for international shipment?
A: Packaging is prepared according to the shipping configuration, with protective measures for the switchgear cabinets, electrical components and associated accessories. Packaging requirements can be coordinated according to the transportation method and project scope.