The KYN61-40.5 35kV High Voltage Switchgear is an indoor metal-clad withdrawable switchgear assembly for three-phase AC power receiving and distribution in 35kV-class systems.
It is configured for incoming and outgoing feeders, bus-tie circuits and transformer-related distribution in indoor substations, power generation facilities and industrial power systems.
Technical Specifications
|
Parameter |
Specification |
|
Model |
KYN61-40.5 |
|
Product Type |
Indoor metal-clad withdrawable switchgear |
|
Rated Voltage |
40.5 kV |
|
Rated Frequency |
50 Hz |
|
Rated Short-Circuit Breaking Current |
20 / 25 / 31.5 kA |
|
Rated Short-Time Withstand Current |
20 / 25 / 31.5 kA, 4 s |
|
Rated Peak Withstand Current |
50 / 63 / 80 kA |
|
Power-Frequency Withstand Voltage |
95 kV / 1 min |
|
Lightning Impulse Withstand Voltage |
185 kV |
|
Auxiliary & Control Circuit Withstand Voltage |
2000 V / 1 min |
|
Control Voltage |
DC/AC 110 V, 220 V |
|
Enclosure Protection |
IP3X |
|
Protection with Door Open |
IP2X |
|
Ambient Temperature |
-15°C to +40°C |
|
Maximum Altitude |
1000 m |
|
Relative Humidity |
≤95% daily average; ≤90% monthly average |
|
Seismic Condition |
Up to magnitude 8 |
|
Installation |
Indoor |
35kV-Class Electrical Design
Equipment Voltage
The 40.5 kV equipment rating is intended for 35 kV-class systems. The applicable system voltage and insulation requirements should be confirmed against the project specification.
Continuous Current
The selected 1250 A, 1600 A, 2000 A or 2500 A rating should match the continuous current specified for the relevant feeder or busbar.
Short-Circuit Level
The selected 20 kA, 25 kA or 31.5 kA breaking and withstand rating should match the calculated fault level of the relevant circuit.
Insulation Level
The specified 95 kV power-frequency and 185 kV lightning impulse withstand levels should be checked against the project's insulation requirements.

Internal Construction
The KYN61-40.5 uses a four-compartment arrangement comprising the instrument room, circuit breaker handcart room, busbar room and cable room.
Circuit Breaker Handcart Room - Houses the withdrawable circuit breaker handcart and its operating mechanism.
Busbar Room - Contains the main bus and busbar bushings, with adjacent cabinet bus sections separated by insulated busbar casing.
Cable Room - Accommodates cable connections, current transformers and the earthing switch required by the specified primary circuit.
Instrument Room -Contains the secondary plug and secondary control, measurement and protection components.
Primary Components - The structure includes the main bus, busbar bushings, contact boxes, current transformers, earthing switch and pressure release device.
Mechanical interlocking is provided between the circuit breaker, earthing switch and cabinet door for the five-prevention function.
Primary Circuit Configurations
Incoming Feeder: Receives power from the upstream 35kV-class system.
Outgoing Feeder: Distributes power to downstream circuits.
Bus Tie: Connects designated bus sections where bus coupling is required.
Isolation: Provides the specified primary circuit isolation arrangement.
Voltage Transformer: Supports voltage measurement and protection functions where required.
Arrester: Provides the specified surge protection arrangement.
Cable / Overhead Connection: Accommodates the primary connection method defined by the project.
Project Configuration & Technical Review
WWE requires project-specific electrical and configuration information before confirming the KYN61-40.5 configuration.
Information required for quotation:
- Single-line system diagram
- System voltage and frequency
- Required rated current
- Short-circuit level
- Main busbar model and specification
- Required configuration functions
- Environmental conditions
- Other special technical requirements
The submitted information is used to review the required switchgear configuration before quotation.

Standards & Compliance
The KYN61-40.5 technical documentation references the following standards:
GB 3906-2006: AC metal-enclosed switchgear and controlgear for rated voltages above 3.6 kV and up to 40.5 kV.
GB/T 11022-2011: Common specifications for high-voltage switchgear and controlgear standards.
IEC 60298:1990: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to 52 kV.
The applicable edition and project-specific standard requirements should be confirmed during technical review.
FAQ
Q: What manufacturing capacity supports the supply of KYN61-40.5 switchgear?
A: The manufacturing base has more than 120 sets of production and testing equipment and an annual output exceeding 10,000 sets of high- and low-voltage switch equipment, motor starting equipment and reactive power compensation panels.
Q: How is the KYN61-40.5 configuration confirmed before order?
A: The configuration is reviewed against the submitted single-line diagram, main busbar specification, required functions, environmental conditions and other project-specific requirements before quotation.
Q: Can the KYN61-40.5 accommodate different primary circuit arrangements?
A: The available arrangements include incoming feeders, outgoing feeders, bus-tie circuits, voltage transformer arrangements, surge arresters, and cable or overhead-line connections. The final combination is determined from the project primary-circuit requirements.
Q: What payment methods are available for the KYN61-40.5?
A: Available payment methods include D/P, D/A, T/T and L/C. The applicable payment terms should be confirmed before order placement.
Q: What is the delivery time for the KYN61-40.5?
A: The stated delivery period is 7–15 days. The final schedule should be confirmed according to order quantity, configuration and project requirements.
Q: What is the MOQ for the KYN61-40.5?
A: The order quantity is confirmed according to the required switchgear lineup, primary circuit arrangement and project scope. The required number of panels should be specified when requesting a quotation.
Q: What warranty is provided for the KYN61-40.5?
A: Manufacturer-caused quality problems identified during the guarantee period are repaired or replaced free of charge. The applicable warranty period and contractual terms should be confirmed before order placement.
Q: Can requirements outside the published operating conditions be considered?
A: Requirements outside the published ambient temperature, altitude, humidity or seismic conditions should be submitted with the inquiry for technical review and confirmation before quotation.
Q: What control voltage options are available for the KYN61-40.5?
A: The available control voltage options are AC/DC 110 V and 220 V. The required control voltage should be specified during technical review.
Q: Can inspection or test documentation be included with the order?
A: The required inspection and technical documentation should be confirmed during project review. Buyers can specify the required inspection records and project documentation when submitting the inquiry.