The KYN28-12 Lv Mv Panels is an indoor metal-enclosed withdrawable low-voltage medium-voltage switchgear panel for three-phase AC power receiving, distribution, and circuit switching.

Technical Specifications
|
Parameter |
Specification |
|
Model |
KYN28-12 |
|
Installation |
Indoor |
|
Construction |
Metal-enclosed, withdrawable |
|
Busbar system |
Single busbar / single busbar sectionalized |
|
Rated voltage |
3 / 6 / 10 kV |
|
Rated frequency |
50 Hz |
|
Rated current |
630 / 1000 / 1250 / 1600 / 2000 / 2500 / 3150 A |
|
Short-time withstand current |
20 / 25 / 31.5 / 40 kA |
|
Peak withstand current |
50 / 63 / 80 / 100 kA |
|
Power-frequency withstand voltage |
42 kV, 1 min |
|
Across-isolation withstand voltage |
48 kV, 1 min |
|
Lightning impulse withstand voltage |
75 kV |
|
Across-isolation impulse withstand voltage |
85 kV |
|
Short-circuit duration |
4 s |
|
Enclosure protection |
IP4X |
|
Internal compartment protection |
IP2X |
|
Ambient temperature |
-15°C to +40°C |
|
Daily average relative humidity |
≤95% |
|
Monthly average relative humidity |
≤90% |
|
Altitude |
≤1000 m |
|
Earthquake magnitude |
≤8 |
|
Applicable standards |
GB 3906; GB/T 11022; DL/T 404; IEC 60694 |
Internal Construction
The KYN28-12 cabinet is divided into four functional compartments, separating withdrawable equipment, busbar connections, cable-side components and secondary control equipment.
Withdrawable Equipment Compartment
Houses the withdrawable circuit-breaker drawer and operating mechanism.
Busbar Compartment
Houses the main busbar and branch busbar connections between adjacent cabinets.
Uses busbar bushings at cabinet-to-cabinet busbar passages.
Cable Compartment
Provides the primary cable connection area.
Accommodates CTs, grounding switches and lightning arresters where required by the selected cabinet arrangement.
Relay and Instrument Compartment
Houses protection, metering, control, monitoring and indication equipment.
Keeps secondary equipment separated from the primary compartments.
Withdrawable Operation and Interlocking
The withdrawable mechanism links drawer position with circuit-breaker operation, primary contact isolation and interlocking functions.
Operating Positions
Working position: The circuit-breaker drawer is connected to the primary circuit for normal operation.
Test/separating position: The primary circuit is separated while the specified testing and control functions remain available.
Interlocking Functions
The drawer cannot be moved when the circuit breaker is switched on in the working position.
The grounding switch cannot be closed while the circuit-breaker drawer remains inside the cabinet.
Specified bottom and rear doors are restricted under the corresponding interlocked condition.
The secondary plug is locked when the drawer is in the working position.
Primary Contact Shutter
The shutter closes over the primary contact area as the drawer moves toward the test/separating position.
The shutter opens as the drawer moves into the working position.
The shutter follows drawer movement rather than relying on separate manual operation.
A monitoring window allows the drawer position to be checked with the cabinet door closed.
Cabinet Design & Protection
Cabinet Construction
Aluminum-zinc alloy sheet is used for the cabinet body and internal partitions.
CNC machining and multi-bending are used for panel fabrication.
Processed panels are assembled by bolting.
Cabinet doors receive electrostatic powder coating.
Earthing Arrangement
An independent TMY40×4 grounding busbar is installed in the cable compartment.
The grounding busbar extends through neighboring cabinets.
The busbar provides electrical continuity between cabinet sections and the cabinet body.
The cabinet grounding arrangement is coordinated with the site's overall earthing system.
Pressure Relief
Pressure-release units are provided above the withdrawable equipment, busbar and cable compartments.
The units provide a release path when pressure rises inside the relevant compartment during an internal electrical fault.


Configuration
The KYN28-12 can be arranged around the feeder functions and electrical scheme defined for the project.
Feeder functions: Incoming feeder, outgoing feeder, transformer feeder, bus coupler and voltage-transformer section.
Primary equipment: Vacuum circuit breaker, CT, VT, grounding switch and lightning arrester where specified.
Secondary equipment: Protection, metering, control, monitoring and indication equipment.
Circuit breaker: VD4 or VS1 configurations are referenced in WWE's current product information; the applicable model is confirmed against the project specification.
Project matching: Final cabinet arrangement is confirmed from the approved single-line diagram and technical requirements.
Quality Control & Inspection
Configuration Verification
Primary and secondary equipment are verified against the approved technical configuration and single-line diagram before assembly is completed. Component selection, cabinet function and equipment arrangement are checked against the agreed project requirements.
Mechanical Verification
Withdrawable positions, interlocking functions and primary contact shutter movement are verified against the specified operating requirements. The relationship between the circuit-breaker position, shutter movement and interlocking functions is checked as part of the mechanical verification.
Documentation & Final Inspection
The completed switchgear is checked against the approved configuration before shipment. Required inspection records, technical documentation and final product information are reviewed to ensure consistency with the agreed project scope.
FAQ
Q: What is the typical MOQ for KYN28-12 switchgear?
A: A typical project order starts from 1 complete switchgear panel, while multi-panel orders are commonly supplied for complete incoming, outgoing, transformer feeder and bus-coupler arrangements.
Q: What is the typical lead time for KYN28-12 switchgear?
A: A typical production lead time is 30–45 days after technical confirmation and order approval, with the final schedule depending on panel quantity and selected components.
Q: What payment terms are available for KYN28-12 switchgear?
A: Common payment terms include T/T, with the specific deposit and balance arrangement agreed in the commercial contract before production.
Q: Can WWE provide drawings for KYN28-12 switchgear approval?
A: General arrangement drawings, electrical schematics and relevant technical drawings can be prepared for customer review and approval according to the agreed project scope.
Q: Can KYN28-12 switchgear be supplied for an EPC or utility project?
A: Yes. Project documentation can be coordinated with EPC specifications, utility requirements and approved electrical drawings, subject to technical clarification before production.
Q: Can customers arrange a pre-shipment inspection for KYN28-12 switchgear?
A: Pre-shipment inspection (PSI) can be arranged before dispatch, with the inspection scope and required records agreed as part of the purchase order.
Q: What technical documents should be submitted when ordering KYN28-12 switchgear?
A: The usual project submission includes the single-line diagram, technical specification, feeder schedule, protection requirements, cable information and applicable project standards, allowing the equipment configuration and drawings to be reviewed before production.
Q: What is WWE's production capacity for high- and low-voltage switchgear?
A: The production facility has more than 120 sets of production and testing equipment and an annual output exceeding 10,000 sets of high- and low-voltage switchgear and related electrical equipment.