The Medium Voltage Switchgear is an indoor metal-enclosed switchgear assembly with a withdrawable vacuum circuit breaker for receiving and distributing three-phase AC power, with circuit switching, protection, control and monitoring functions.

Technical Specifications
|
Parameter |
Specification |
|
Product Type |
Indoor fixed metal-enclosed medium voltage switchgear |
|
Electrical System |
Three-phase AC |
|
Rated Voltage |
3 / 6 / 10 kV |
|
Rated Frequency |
50 Hz |
|
Rated Current |
630 / 1000 / 1250 / 1600 / 2000 / 2500 / 3150 / 5000 A |
|
Rated Short-Time Withstand Current |
20 / 25 / 31.5 / 40 kA |
|
Rated Peak Withstand Current |
50 / 63 / 80 / 100 kA |
|
Short-Circuit Duration |
4 s |
|
Power-Frequency Withstand Voltage |
42 kV / 48 kV, 1 min |
|
Lightning Impulse Withstand Voltage |
75 kV / 85 kV |
|
Enclosure Protection |
IP4X |
|
Internal Compartment Protection |
IP2X |
|
Installation |
Indoor |
|
Ambient Temperature |
-15°C to +40°C |
|
Daily Average Relative Humidity |
≤95% |
|
Monthly Average Relative Humidity |
≤90% |
|
Maximum Installation Altitude |
≤1000 m |
|
Seismic Requirement |
Up to magnitude 8 |
Note: The 5000 A switchgear rating requires confirmation of the applicable primary equipment and busbar configuration before order approval.
Cabinet Layout
Circuit Breaker Section: Houses the withdrawable vacuum circuit breaker handcart, static contact assembly, secondary plug and breaker operating mechanism.
Busbar Section: Contains the main busbar, branch busbars, busbar bushings and insulating components.
Cable Section: Provides space for cable connections and primary components installed according to the selected electrical configuration.
Relay & Instrument Section: Houses protection, control, indication and secondary circuit equipment separately from the primary circuit sections.
Circuit Breaker & Five-Prevention
Withdrawable Vacuum Circuit Breaker
The switchgear uses a withdrawable vacuum circuit breaker handcart for primary circuit switching and isolation. The handcart can be withdrawn from the primary circuit for servicing or replacement.
VS1 and VD4 Options
VS1 and VD4 series vacuum circuit breakers can be specified according to the required electrical rating and final switchgear configuration.
Five-Prevention Interlocking
The five-prevention interlocking system is designed to prevent incorrect circuit breaker operation, movement of the breaker handcart under load, closing the grounding switch while the circuit is energized, closing the circuit breaker with the grounding switch closed, and incorrect access to an energized compartment.
Breaker Connection
The breaker handcart is connected to the primary circuit through the static contact assembly, while the secondary plug provides the connection for the breaker-related secondary circuits.
Protection & Auxiliary Components
Current Transformer: Provides current measurement and protection inputs for the protection system.
Grounding Switch: Provides grounding of the designated circuit during maintenance operations.
Lightning Arrester: Provides surge protection where specified by the electrical configuration.
Protection & Control Equipment: Provides the protection, control and indication functions required by the secondary circuit.
Heater: Can be added to the relay or cable compartment where specified for moisture and condensation control.
Pressure-Release Device: Provides a designated pressure-release path within the cabinet.
Grounding Main Busbar: Provides the main grounding connection within the cabinet.
Applications
Incoming Power Distribution
The switchgear can be used as an incoming medium voltage panel for receiving electrical power and transferring it to the internal busbar system.
Outgoing Feeder Protection
Outgoing feeder panels can distribute medium voltage power to downstream loads while integrating the required circuit breaker, current transformer and protection equipment.
Transformer Feeder
A switchgear section can be configured as a transformer feeder with the required switching, protection and measurement components.
Bus Section and Coupling
The cabinet arrangement can be used for bus section or coupling functions where the project single-line diagram requires sectionalized medium voltage distribution.

Configuration & Ordering Information
Technical confirmation requires project-specific electrical, mechanical and installation information rather than only the requested voltage and current ratings.
Please provide:
Main wiring scheme, single-line diagram, range diagram and switchgear arrangement plan.
Secondary circuit wiring diagram and terminal arrangement diagram.
Type, specification and quantity of the required electrical components.
Main and branch busbar specifications and materials.
Required accessories and spare parts.
Special electrical, mechanical, environmental or installation requirements.
The final configuration is confirmed based on the approved electrical scheme, component requirements, busbar specification and site conditions.
FAQ
Q: What is the typical lead time for medium voltage switchgear?
A: Standard configurations typically require about 30–45 days for production after order confirmation. Project-specific configurations may require additional time for technical approval.
Q: What payment terms are available for medium voltage switchgear?
A: Common international trade terms include a deposit before production with the balance paid before shipment. Exact payment terms are stated in the sales contract.
Q: What warranty is provided for medium voltage switchgear?
A: A 12-month warranty from shipment is commonly provided for manufacturing defects, subject to the agreed warranty terms.
Q: What standards does the medium voltage switchgear comply with?
A: The switchgear can be manufactured to applicable GB3906 and IEC298 requirements specified for the project. The applicable standards and technical requirements should be confirmed during order review.
Q: Can pre-shipment inspection be arranged?
A: Yes. Pre-shipment inspection can be arranged according to the agreed inspection requirements before shipment.
Q: What is the manufacturing capacity of Worldwide Electric?
A: Worldwide Electric operates a manufacturing base of more than 200,000 m² with over 120 production and testing equipment sets and reports annual production exceeding 10,000 sets of related electrical equipment.
Q: How is medium voltage switchgear manufactured?
A: The switchgear cabinet is manufactured from aluminum-zinc alloy sheet using CNC machining and multi-bending forming processes, followed by bolted assembly.