Medium voltage switchgear is an indoor metal-enclosed, withdrawable assembly for controlled switching, protection and distribution in three-phase AC medium voltage networks.
Technical Specifications
|
Parameter |
Specification |
|
Product Type |
Indoor metal-enclosed withdrawable medium voltage switchgear |
|
Rated Voltage |
3 / 6 / 10 kV |
|
Rated Current |
630 / 1000 / 1250 / 1600 / 2000 / 2500 / 3150 / 5000 A |
|
Rated Frequency |
50 Hz |
|
Rated Short-Time Withstand Current |
20 / 25 / 31.5 / 40 kA |
|
Rated Peak Withstand Current |
50 / 63 / 80 / 100 kA |
|
Rated Short-Circuit Duration |
4 s |
|
Rated Power-Frequency Withstand Voltage |
42 kV, 1 min |
|
Power-Frequency Withstand Across Isolating Gap |
48 kV, 1 min |
|
Rated Lightning Impulse Withstand Voltage |
75 kV |
|
Lightning Impulse Withstand Across Isolating Gap |
85 kV |
|
Enclosure Protection |
IP4X |
|
Internal Compartment Protection |
IP2X |
|
Ambient Temperature |
-15°C to +40°C |
|
Relative Humidity |
Daily average ≤95%; monthly average ≤90% |
|
Installation Altitude |
≤1000 m |
|
Circuit Breaker |
Withdrawable vacuum circuit breaker |
|
Installation |
Indoor |
Main Components
The switchgear integrates primary switching, power distribution, measurement, grounding and protection equipment within separate functional compartments.
Vacuum Circuit Breaker
The withdrawable vacuum circuit breaker controls the primary feeder circuit and interrupts fault current when a protection trip command is issued.
Main Busbar
The main busbar connects individual panels and distributes power between incoming and outgoing circuits.
Current Transformers
Current transformers provide current signals to protection and metering equipment. CT ratio and accuracy class are selected according to the feeder requirements.
Voltage Transformers
Voltage transformers provide voltage signals for protection, measurement and metering where required.
Earthing Switch
The earthing switch connects the designated isolated circuit section to earth under the specified operating conditions.
Protection Relay
The protection relay processes signals from the CTs and VTs and sends a trip command to the circuit breaker when a configured protection condition is detected.
How a Switchgear Line-Up Is Configured

A switchgear line-up consists of individual panels assigned to different circuit functions.
Incoming Feeder Panel:Connects the incoming medium-voltage supply to the main busbar.
Outgoing Feeder Panel:Connects the main busbar to downstream distribution circuits.
Transformer Feeder Panel:Connects and protects a transformer circuit within the line-up.
Bus Coupler Panel:Connects two busbar sections when sectionalized bus operation is required.
PT / Metering Panel:Provides voltage measurement or metering where specified.
The panel arrangement is established from the project single-line diagram and feeder schedule rather than from a fixed panel sequence.
Cabinet Construction
The cabinet is divided into functional sections to separate the main electrical circuits and secondary equipment.
Busbar Compartment
The main and branch busbars are installed in the dedicated busbar section. The busbar arrangement corresponds to the specified current rating and line-up configuration.
Circuit Breaker Compartment
The withdrawable vacuum circuit breaker is installed on a movable handcart. The withdrawable arrangement allows the breaker to be positioned according to the required operating condition.
Cable Compartment
The cable section accommodates the specified cable connections and associated primary components, including current transformers and earthing equipment where configured.
Low-Voltage / Relay Compartment
Protection relays, meters, control components, terminal blocks and secondary connections are arranged in the relay instrument section.
Manufacturing Process
The cabinet is produced through sheet-metal fabrication, busbar processing, primary component assembly, secondary wiring and mechanical integration.
Enclosure Fabrication
Metal panels and internal partitions are processed according to the cabinet drawings. Aluminum-zinc alloy panels are assembled with bolted connections. CNC machining and multi-bending processes are used for the cabinet structure.
Busbar Fabrication
Copper busbars are cut, bent and drilled according to the required current rating and electrical arrangement. Connection points are processed to match the approved panel configuration.
Primary Component Assembly
The vacuum circuit breaker, insulating components, current transformers, voltage transformers, earthing switch and other specified primary components are installed in their designated compartments.
Secondary Wiring
Protection relays, meters, control devices, terminal blocks and auxiliary components are installed according to the secondary wiring diagrams. Wires are routed, identified and terminated at the specified terminals.
Mechanical Integration
The breaker truck, operating mechanism, shutters, doors and interlocking components are assembled with the cabinet structure according to the specified mechanical arrangement.


Standards & Factory Verification
IEC 62271-200 provides the applicable IEC framework for the specified metal-enclosed AC switchgear above 1 kV and up to 52 kV. GB 3906 is applied where required by the project specification.
The applicable standard, electrical ratings and approved drawings are confirmed before production.
Verification Before Shipment
Each completed panel is checked against the approved drawings and component list.
Configuration and Mechanical Checks
- Cabinet dimensions
- Component models and nameplate data
- Primary circuit connections
- Secondary wiring and terminal connections
- Circuit breaker operation
- Withdrawable mechanism movement
- Mechanical interlocking
- Control and indication functions
Electrical Tests
Specified electrical tests
Inspection and test records are prepared according to the verification activities completed for the specific order.

FAQ
Q: What are the operating positions of a withdrawable vacuum circuit breaker?
A: The withdrawable circuit breaker can be positioned in connected, test and disconnected positions. Each position defines the breaker's connection to the primary circuit and associated control circuits.
Q: How does the mechanical interlocking system work?
A: The interlocking mechanism coordinates breaker movement, earthing operation and access to designated sections. It prevents specified operations when the required operating condition has not been established.
Q: What drawings are normally provided for a switchgear project?
A: The document package can include a general arrangement drawing, single-line diagram, secondary wiring diagram, terminal diagram, component list and technical specification. Inspection and test records are provided according to the agreed verification scope.
Q: What is the minimum order quantity for medium voltage switchgear?
A: MOQ depends on the switchgear configuration and panel quantity. The required quantity is confirmed according to the project scope and technical configuration.
Q: How is medium voltage switchgear packaged and shipped?
A: Panels are secured and protected according to their dimensions, weight, quantity, transportation method and destination. Individual panels or complete line-ups are prepared according to the agreed shipment arrangement.