The KYN61-40.5 Medium Voltage Metal Clad Switchgear is a 40.5 kV metal-clad withdrawable switchgear assembly for three-phase AC power receiving, distribution and circuit switching.

Technical Specifications
|
Parameter |
Specification |
|
Model |
KYN61-40.5 |
|
Product Type |
Metal-clad withdrawable medium voltage switchgear |
|
Rated Voltage |
40.5 kV |
|
Rated Frequency |
50 Hz |
|
Rated Current |
1250 / 1600 / 2000 / 2500 A |
|
Rated Short-Time Withstand Current |
20 / 25 / 31.5 kA, 4 s |
|
Rated Peak Withstand Current |
50 / 63 / 80 kA |
|
Rated Short-Circuit Breaking Current |
20 / 25 / 31.5 kA |
|
Power-Frequency Withstand Voltage |
95 kV, 1 min |
|
Lightning Impulse Withstand Voltage |
185 kV |
|
Enclosure Protection |
IP3X |
|
Compartment Protection with Door Open |
IP2X |
|
Ambient Temperature |
-15°C to +40°C |
|
Maximum Altitude |
≤1000 m |
|
Daily Average Relative Humidity |
≤95% |
|
Monthly Average Relative Humidity |
≤90% |
|
Seismic Rating |
Up to magnitude 8 |
Metal-Clad Compartmentalized Construction
The KYN61-40.5 is divided into four defined areas: instrument room, handcart room, busbar room and cable room.
Instrument room: Accommodates the secondary equipment arrangement shown in the switchgear structure.
Handcart room: Houses the withdrawable circuit breaker handcart.
Busbar room: Contains the main busbar and busbar bushing.
Cable room: Accommodates the cable connection, current transformer and earthing switch.
Withdrawable Circuit Breaker Arrangement
The KYN61-40.5 uses a withdrawable circuit breaker handcart installed in a dedicated handcart compartment.
Circuit Breaker: Withdrawable circuit breaker handcart
Breaker Compartment: Dedicated handcart room
Primary Connection: Contact box
Secondary Connection: Secondary plug
Circuit Breaker Compatibility: VS1 / VD4 series

Project Configuration
The final KYN61-40.5 lineup is based on the customer's single-line diagram, feeder arrangement and protection requirements.
Control Circuit Voltage: DC 110 / 220 V; AC 110 / 220 V
Single-Line Diagram: Incoming, outgoing, transformer feeder and bus-coupler arrangement
Feeder Schedule: Panel quantity and feeder arrangement
Transformer Feeder Requirements: Transformer feeder electrical requirements
CT / VT Requirements: Current and voltage transformer requirements for measurement and protection
Protection Requirements: Required protection functions and relay configuration
Cable Arrangement: Cable connection and entry requirements
The approved single-line diagram and feeder schedule are used to confirm the final lineup before production.
Applications
Substation Distribution
Incoming and outgoing feeder panels for indoor 40.5 kV substations.
Transformer Feeders
Medium voltage feeder panels connecting the switchgear lineup with transformers.
Bus Coupling
Bus-coupler panels for connecting or separating two bus sections.
Engineering & Factory Support
We provide technical drawing, manufacturing, commissioning and warranty support for medium voltage switchgear projects.
Technical Drawing: We provide drawing design for project-specific switchgear configurations based on the confirmed technical requirements.
Manufacturing: We manufacture medium voltage switchgear at our manufacturing facility, covering switchgear assembly production for project orders.
Production & Testing Equipment: Our manufacturing operations include more than 120 sets of production and testing equipment.
Factory Inspection: We carry out production and inspection activities at our manufacturing facility before shipment. Inspection and testing records can be provided according to the confirmed project requirements and documentation scope.
Commissioning: We provide commissioning support for medium voltage switchgear projects after installation.
Warranty Responsibility: If a quality problem is confirmed to be caused by our manufacturing during the warranty period, we provide repair or replacement according to the warranty terms.
FAQ
Q: What is the MOQ for KYN61-40.5 switchgear?
A: The MOQ is 1 set. Multiple panels can be supplied as one complete switchgear lineup for a project.
Q: What is the typical lead time for KYN61-40.5 switchgear?
A: The typical production lead time is 30–45 days after the technical configuration, drawings and order details are confirmed.
Q: What payment terms are available for KYN61-40.5 switchgear?
A: T/T and L/C are available for KYN61-40.5 switchgear orders. The payment schedule is confirmed in the commercial quotation and order contract.
Q: What technical documents can WWE provide for KYN61-40.5 switchgear?
A: We provide technical drawings and project documentation according to the confirmed technical requirements and document list.
Q: Can WWE prepare switchgear drawings for project approval?
A: Yes. We provide drawing design for project-specific switchgear configurations before production.
Q: What information should I provide when requesting a KYN61-40.5 quotation?
A: Provide the required panel quantity, single-line diagram, feeder schedule, required electrical ratings, control voltage and applicable project specification when available. This information allows us to prepare the technical and commercial quotation.
Q: Can KYN61-40.5 switchgear be supplied as a complete lineup?
A: Yes. Multiple panels can be supplied as one complete lineup for incoming, outgoing, transformer feeder and bus-coupler circuits.
Q: What is the warranty for KYN61-40.5 switchgear?
A: Manufacturing-caused quality problems identified during the warranty period are subject to repair or replacement according to the warranty terms.
Q: Does WWE provide commissioning support for KYN61-40.5 switchgear?
A: Yes. We provide commissioning support for medium voltage switchgear projects after installation.
Q: How is KYN61-40.5 switchgear prepared for international shipment?
A: Export packaging and shipment arrangements are confirmed according to the equipment configuration, transportation requirements and destination.