The GZDW DC Power Supply Panel integrates AC input, high-frequency rectification, battery charging and DC distribution into a single auxiliary DC power system.
It supplies controlled DC power to protection, switching, control and secondary electrical circuits in substations, power plants, hydropower stations and industrial electrical facilities.

Technical Specifications
|
Parameter |
Specification |
|
Product Type |
DC Power Supply Panel |
|
Series |
GZDW Series |
|
AC Input Configuration |
Two circuits, three-phase four-wire main and reserve supply |
|
Rated AC Input Voltage |
380 VAC ±10% |
|
AC Frequency |
50 Hz ±5% |
|
Rated DC Output Voltage |
110 VDC / 220 VDC |
|
Rated Output Current |
6 A, 10 A, 12 A, 20 A, 30 A, 40 A, 50 A, 60 A, 70 A, 80 A, 90 A, 100 A, 120 A, 130 A, 150 A, 180 A, 200 A, 260 A, 300 A, 400 A |
|
Battery Capacity |
10 Ah–3000 Ah |
|
Battery Options |
Lead-acid or nickel-cadmium configurations |
|
Operating Mode |
Continuous operation |
|
Charging Technology |
High-frequency switching rectifier |
|
Rectifier Configuration |
Modular; N+1 redundancy available |
|
Protection Functions |
Input/output overvoltage and undervoltage protection, output overcurrent and short-circuit protection, thermal protection |
|
240D05A Module Input Voltage |
300–456 VAC |
|
240D05A Stabilized Voltage Accuracy |
≤0.5% at 20–100% load and 300–456 VAC input |
|
240D05A Stabilized Current Accuracy |
≤0.5% at 20–100% load and 300–456 VAC input |
|
240D05A Charging Efficiency |
88–91% at 300 VDC / 5 A output |
|
240D05A Dynamic Response |
12–100 μs under a 20–75% load change |
|
Module Operating Temperature |
-15°C to +45°C for the specified module configuration |
|
Module Storage Temperature |
-40°C to +60°C for the specified module configuration |
|
Relative Humidity |
Daily average ≤95%; monthly average ≤90% |
|
Maximum Installation Altitude |
≤2400 m |
|
Complete Appliance Noise |
<55 dB |
240D05A Module Data
The 240D05A specifications above apply to the individual rectifier module under the stated test conditions. They are not complete-panel performance ratings. Complete-panel capacity and operating performance depend on the number of rectifier modules installed and the approved system configuration.
DC Loads Covered by the System
The DC power supply panel is configured around auxiliary circuits that require a controlled DC source. Connected loads are defined by the project's electrical load schedule.
Circuit Breaker Operation
DC feeders supply breaker trip and closing circuits required for electrical switching operations.
Relay Protection
The DC system supplies protection relays and associated secondary circuits that require continuous auxiliary power for protective operation.
Switchgear Control
Dedicated DC feeders supply control, interlocking and indication circuits defined in the approved switchgear design.
Signaling and Secondary Equipment
Additional DC feeders can supply signaling, alarm, measurement and other secondary equipment included in the project's approved load schedule.
System Configuration
The GZDW DC Power Supply Panel is arranged around the following power path:
AC Input → Rectifier/Charger → DC Bus → DC Distribution → Connected Loads
AC Input
The standard configuration uses two three-phase four-wire AC input circuits for main and reserve supplies.
Rectifier/Charger
High-frequency switching rectifier modules convert AC input into regulated DC power and provide the charging source for the connected battery.
DC Bus
The DC bus provides the common connection between the rectifier section, battery and outgoing DC distribution.
DC Distribution
The distribution section separates the outgoing DC circuits required by the project. Circuit quantity and feeder ratings are established from the purchaser's electrical drawings and load schedule.
Rectifier and Battery System
The rectifier modules and battery form the DC supply and stored-energy section of the panel. Rectifier capacity and battery configuration are established from the project's electrical load and operating requirements.
Modular Rectifier Configuration
Plug-in rectifier modules operate in parallel to provide the required DC capacity. The installed module quantity is determined from the calculated operating load and the selected redundancy requirement.
N+1 Redundancy
An N+1 arrangement provides one additional rectifier module beyond the quantity required for the calculated operating load. If one module is removed from service, the remaining modules are configured to maintain the required operating capacity, subject to the approved system design.
Battery Charging
The charging section supports floating and equalizing charging modes for applicable battery configurations. Charging parameters are established according to the selected battery technology and approved system configuration.
AC Failure and Battery Backup
During normal AC operation, the rectifiers supply the DC load and maintain the battery in its specified charging condition. When the normal AC supply is interrupted, the battery supplies the DC bus and continues to feed the connected DC circuits.
Protection and Monitoring
The control and monitoring section provides status information and alarm indications for the rectifier, battery and DC supply system.
Rectifier Monitoring
Individual rectifier modules can be monitored for operating and fault status, allowing module-level abnormalities to be identified within the modular configuration.
Battery Monitoring
Battery charging and operating conditions are monitored through the system control and alarm functions.
Communication and Remote Monitoring
Communication and remote monitoring requirements are defined during project configuration according to the purchaser's control architecture.
Project Engineering Configuration
The Power Supply Panel is configured from project electrical data rather than selected solely from a standard cabinet model.
The key information required for configuration includes:
- DC system voltage
- Continuous DC load current
- Required backup duration or battery capacity
- AC input arrangement
- Number and rating of outgoing DC circuits
- Battery technology
- Rectifier redundancy requirement
- Monitoring and communication requirements
- Installation environment
- Applicable project requirements
- Required technical documentation
These inputs are used to determine the required rectifier capacity and module quantity, battery configuration, DC distribution arrangement and cabinet configuration.
For projects with engineering documentation, the proposed configuration can be reviewed against the submitted load schedule, single-line diagram and other applicable electrical documents before production release.
Factory Quality Control
The Power Supply Panel is assembled and tested against its approved project configuration before shipment. Quality control covers component verification, cabinet assembly checks, electrical verification, functional testing and full-system aging.
Component and Assembly Control
Electrical components are checked against the approved project configuration before assembly. Cabinet production includes component mounting, busbar connection, internal wiring, terminal connection and circuit identification.
Electrical Verification
Completed panels are checked for wiring accuracy, polarity, insulation and circuit continuity before functional testing.
Functional Testing
Rectifier operation, battery charging functions, configured protection functions and alarm functions are checked against the specified operating requirements.
48-Hour Full-Load Aging
The complete assembled appliance undergoes a 48-hour high-temperature full-load aging test according to the specified production procedure. The test is performed on the complete panel before shipment rather than only on individual rectifier modules.
Manufacturing Capability
Worldwide Electric operates a production base covering more than 200,000 m², with more than 120 sets of production and testing equipment. The facility has an annual production capacity exceeding 10,000 sets of high- and low-voltage switchgear, motor starting equipment and reactive power compensation panels.
FAQ
Q: What is the minimum order quantity (MOQ) for the GZDW DC Power Supply Panel?
A: Single-panel orders can be quoted for project requirements. MOQ is confirmed according to the required configuration, quantity and supply scope.
Q: What is the typical lead time for a GZDW DC Power Supply Panel?
A: Lead time is confirmed after the technical configuration and order scope are finalized. The production schedule depends on the panel configuration, component requirements, battery arrangement and order quantity. The confirmed lead time is stated in the quotation or order confirmation.
Q: Can the GZDW DC Power Supply Panel be supplied for OEM or private-label projects?
A: OEM project supply can be discussed according to the required equipment configuration, nameplate information, documentation and project supply scope. Requirements should be confirmed before quotation.
Q: Can replacement rectifier modules and other spare parts be supplied separately?
A: Replacement rectifier modules and specified electrical components can be supplied according to the installed configuration. Providing the original model, equipment data or previous order information helps identify the required replacement component.
Q: Can additional rectifier modules be added to an existing system?
A: Additional modules can be evaluated according to the installed rectifier configuration, available cabinet capacity, DC load requirement and system design. The existing system configuration should be reviewed before confirming compatibility.
Q: Can the DC power supply panel be supplied as a replacement for an existing system?
A: Replacement projects can be evaluated using the existing panel's technical data, drawings, load information and battery requirements. The replacement configuration should be checked against the existing DC system before production.
Q: How is the warranty period determined for the GZDW DC Power Supply Panel?
A: Warranty terms are specified in the commercial quotation and order documentation. The applicable warranty scope and period are confirmed according to the equipment supplied and the agreed project terms.
Q: What information should be included when requesting a replacement or repeat order?
A: The previous equipment model, nameplate data, order reference, existing drawings or configuration records can be provided when available. These details help verify the required configuration before quotation.