The Battery & Charger Panel is a GZDW-series DC power supply and battery charging cabinet for station DC systems in substations, power plants and power distribution facilities.
Technical Specifications
|
Parameter |
Specification |
|
Product name |
Battery & Charger Panel |
|
Product series |
GZDW |
|
AC input arrangement |
Dual three-phase four-wire main and standby supplies |
|
Rated AC input voltage |
380 V ±10% |
|
AC frequency |
50 Hz ±5% |
|
Rated DC output voltage |
110 V / 220 V |
|
Rated DC output current |
6–400 A |
|
Battery capacity |
10–3000 Ah |
|
Charger module |
240D05A |
|
Charger input range |
300–456 VAC |
|
Adjustable charger output |
180–300 VDC |
|
Stabilized voltage accuracy |
0.01% representative / 0.5% max. |
|
Stabilized current accuracy |
0.08% representative / 0.5% max. |
|
Dynamic response |
12–100 μs; 50 μs representative |
|
Charger efficiency |
88–91% |
|
Ripple factor |
0.01–0.1% |
|
Dielectric strength |
1500 VAC, 50 Hz, 1 min |
|
Starting delay |
1–3 s |
|
Parallel current imbalance |
±0.5% min. / ±2% representative / ±5% max. |
|
Continuous load operation |
100% rated output current within the specified float-charge voltage range |
|
Charger module service temperature |
-15°C to +45°C |
|
Panel operating temperature |
-10°C to +45°C |
|
Storage temperature |
-40°C to +60°C |
|
Relative humidity |
Daily average ≤95%; monthly average ≤90% |
|
Altitude |
≤2400 m |
|
Seismic resistance |
Up to magnitude 8 |
|
Noise level |
<55 dB |
Battery Charging & DC Supply
Regulated DC Supply
The charger converts the AC input into regulated DC power for station protection, control and auxiliary circuits.
Battery Charging
The charger supplies the DC system while maintaining the connected battery under the required float-charging or equalizing-charging condition.
Battery Backup
When the charger AC supply is unavailable, the connected battery supports the DC loads according to the battery capacity and station DC system design.
System Relationship
AC Supply → Battery Charger → DC System → DC Loads
Charging & Protection Functions
Automatic Current Limitation
The charger limits output current under overload conditions to prevent uncontrolled current increase.
Input Overvoltage Protection
The charger monitors the AC input and protects the charging module against defined input overvoltage conditions.
DC Output Overvoltage Protection
The charger monitors the DC output and protects connected loads against defined output overvoltage conditions.
Short-Circuit Protection
The charger protects the DC output against short-circuit conditions and automatically recovers after the fault is removed.
Battery Configuration
Battery Type
The GZDW configuration supports lead-acid and nickel-cadmium batteries. The selected battery type determines the applicable charging settings.
Cell Configuration
The required charging voltage is determined by the battery chemistry and cell arrangement, with different float-charge and equalizing-charge values applicable to different configurations.
Charging Mode
Float charging maintains the battery at its normal standby charging condition, while equalizing charging applies the higher charging condition required by the selected battery configuration.
Factory Inspection & Quality Control
Configuration Verification
The finished panel is checked against the confirmed technical configuration and approved project requirements.
Electrical Inspection
Inspection covers internal wiring, electrical connections, charger operation and DC output according to the agreed inspection scope.
Functional Verification
Charging and applicable protection functions are verified before shipment against the approved technical requirements.
Inspection Records
Inspection and test records can be provided according to the agreed project documentation requirements.
FAQ
Q: What is the minimum order quantity for a Battery & Charger Panel?
A: The minimum order quantity is 1 set. Single-unit orders are accepted for project requirements, replacement equipment and evaluation purposes.
Q: What is the typical production lead time?
A: The typical production lead time is 30–45 days after the technical specifications, drawings and order details are confirmed. The final schedule depends on the confirmed configuration and order quantity.
Q: What payment terms are available?
A: The standard payment term is 30% T/T as a deposit and 70% T/T before shipment. Other arrangements can be discussed for specific project requirements.
Q: What Incoterms are available for international orders?
A: Orders can be quoted under EXW, FOB or CIF terms. The applicable Incoterm is confirmed according to the destination, shipping arrangement and purchase contract.
Q: What warranty is provided for the Battery & Charger Panel?
A: WWE provides a 12-month warranty against manufacturing defects under normal operating conditions, subject to the agreed sales contract.
Q: Can I arrange a pre-shipment inspection?
A: Yes. Pre-shipment inspection can be arranged before shipment, with the inspection scope and applicable test items agreed during order confirmation.
Q: Can third-party inspection be arranged?
A: Yes. Third-party inspection can be arranged when required by the purchaser or project specification. The inspection agency, scope and associated costs should be confirmed before the inspection date.
Q: Can spare parts be supplied after delivery?
A: Yes. Replacement parts can be supplied according to the actual equipment configuration. The component model or identification should be provided when requesting a replacement part.
Q: How do I request after-sales technical support?
A: Provide the equipment model, order information, problem description and relevant operating or test information so WWE can identify the supplied configuration and assess the reported issue.
Q: What information is required for a Battery & Charger Panel quotation?
A: Provide the AC supply, DC voltage and load, battery type and capacity, cell arrangement, charging requirements, outgoing circuits and installation conditions. For replacement projects, existing charger data, battery data or electrical drawings are also required.
Q: Does WWE manufacture Battery & Charger Panels in-house?
A: Yes. WWE assembles the panel according to the confirmed electrical configuration. The production facility has more than 120 sets of production and testing equipment, including more than 50 sets identified by WWE as reaching an advanced level in China.